Choosing the right fieldbus
Editor's Note: This article provides additional information to the feature on Merging AC drives
and Fieldbus Technology that appeared in the Feb. 2002 issue of Machinery & Equipment MRO.
The main feature article can be found in the Feb. 2002 issue archive on www.mro-esource.com for
further reference.
How do you find the ideal fieldbus for your needs? There is no single fieldbus that can fulfill
all requirements for every application. There can be considerable differences in communication
requirements for different applications, therefore the fieldbus must be selected according to these
requirements.
Most users want to select a simple communication method that fulfils the requirements of their
application. The selected standard is supposed to have appropriate devices and tools for the application.
Apart from ensuring that the chosen device can accept multi-vendor products, users should consider
the following:
* Topology
* Access to the fieldbus
* Physical features
* Protocol
* Access rights in multimaster systems
* Noise immunity
* Transmission speed.
Other consideration needs to be given to the technical, communications and system safety requirements.
For a complete list, visit the Online Features section of www.mro-esource.com and click on "Choosing
the right fieldbus."
Below is a checklist to consider:
Number of nodes
This is the number of devices connected to the field bus or bus segment. This varies from a maximum
of 64 nodes with DeviceNet to 247 nodes with Modbus. If, for example, you have an application with
100 drives and want to control from DeviceNet then you will need two DeviceNet scanners.
Transmission speed
Also referred to as Baud rate. The higher the transmission speed the shorter the bus length. The
maximum bus segment cable length is defined in the fieldbus standard, such as DeviceNet, Profibus
etc., for the supported Baud rates.
Extent of user data
The extent of user data can be limited, depending on either hardware (ASICs, defined by node manufacturer)
or software (protocol, defined by the fieldbus standard). This is usually defined in the fieldbus
node User Manual.
Topology
The topology usually comes with rules defining how the nodes are connected to one another. The
topolgy also defines bus termination rules. This is defined by the fieldbus standard and can be
bus, ring, star topology etc.
Modularity, expansion possibilities
Because there is a single cable, the system can be easily constructed in a modular way. This allows
the system to be easily expanded later. Machine manufacturers can build their systems based on
a modular concept (flexibility).
Noise immunity
Due to reduced amount of cabling there is much less chance to pick up disturbances. Digital technology
means drift is eliminated.
Cable requirements
These are defined by the fieldbus standard. Each fieldbus type has its own cable requirements,
for example, cross-sectional area, impedance, stray capacitance, etc
Connection cost
Connecting a single cable is much easier than connecting a variety of analogue signal cables. The
method of connection is usually standardised.
Device replacement without bus interruption
In daisy-chain bus topology, the bus cable can be removed from the device without interrupting
the bus communication. With point-to-point or ring connection, bus communication will always be
lost.
Requirements of the application
Type of fieldbus is selected according to the response time required by the application and/or
the amount of nodes to be connected to the system
Communication
Required data transfer capacity
Usually the amount of I/O data to be exchanged via the bus
Guaranteed response time
Depending on the bus cycle time, determined by the amount of connected nodes, selected transmission
speed and extent of data frame
SYSTEM SAFETY
System safety in a fault situation
Usually the standard fieldbus topology is not redundant but can be made so in many cases. In none
redundant bus systems, the action in case of a communication loss can be configured within the
nodes, for example fault or remain in operation etc
Safety of data transfer (error recognition)
The safety of the data transfer differs from fieldbus to fieldbus and is defined within the fieldbus
protocol
Special attention towards power supply solutions
Some fieldbus systems supply the nodes via the fieldbus cable (DeviceNet) and others require an
external power supply (Profibus) to feed the nodes
Readiness of diagnostic tools
For the open fieldbus standards a large variety of diagnostic tools from several manufacturers
are available
This information was compiled by ABB Inc., Automation Technology Products Division, Saint-Laurent,
QC H4S 1N6 Canada. For more information, tel. 514-832-6573, fax 514-332-0609, or visit www.abb.com/motors&drives.